Hot Water Baseboard Cold Zone Valve Clicking Repair
The HVAC Hacker The HVAC Hacker
31K subscribers
3,932 views
0

 Published On Dec 2, 2021

I am on a no heat service call. One zone on a hot water boiler isn’t heating and hot water baseboards are cold. I find the thermostat sending power to the zone valve. The zone valve energizes yet fears are stripped. Causing the zone valve to click and not open. Therefore I have to replace the zone valve.